110609 Site Visit- Building Control Inspection
Light sensor to external elevation- CVA to check NEE drawings
Light sensor to external elevation- CVA to check NEE drawings
'Fire Door Keep Shut' signs to be changed to 'Fire Door Keep Clear' where operated with hold-open device
Green Fire Escape graphics still required to Push bar exits in all locations
Minstrel's gallery gate- Hasp detail to be remade to provide fixing for master gate as detail
Ditto
Mastic still required to Fineline glazing- kitemark not visible- HCL to confirm glazing fitted
'Fire Door Keep Shut' signs to be changed to 'Fire Door Keep Clear' where operated with hold-open device
Max 380mm difference between gravel fill and FFL of paving to perimeter detail Otway House
Manifestations- TBA w/ School
Benches to be fitted to low headroom areas- Manifestations not required GFL Stair 1 & 2 CL
Green Fire Escape graphics still required to Push bar exits in all locations
40mm clearance required around handrails- window lining currently obstructing
Graphics required to disabled WC alarm lights- fitted to bulkhead 1FL office CL
Bright trim still required to differentiate ramp- CL link
Kite mark required for glass to balustrade- HCL
Electromagnet hot- Action AC Leigh/ HCL